When performing preventive
maintenance on switchgear,
particularly Infrared (IR)
thermography, one needs to
power down, open up, disassemble, and reenergize
the switchgear. Then make measurements
while it’s open! Scary! I haven’t
spoken to a single engineer or electrician
that looks forward to that moment. Or the
time required in front of open cabinets to
take the IR thermography shots.
This mechanical intrusion into the
switchgear, especially metal enclosed
switchgear, removes all safety barriers designed
into the switchgear just so the bus
bars and the connections can be visible for
an IR thermography shot.
This mechanical intrusive, labor-intensive
work while the switchgear is de-energized,
can be the catalyst that changes
a minor problem to an arc flash hazard.
With all safety barriers removed, and
the mechanical intrusion, the time of reenergizing
the switchgear becomes a time
of great concern, second only to the time
the switchgear is re-energized after being
completely reassembled and being put
back online.
The arc flash threat itself is not predicated
on the load current, but the condition
of the mechanical connections of the
bus bars and other connections, and the source impedance of the power feed. But
the load current is critical to finding a
marginally bad connection that will be a
source of a failure later on that can grow
into a potential arc flash hazard during another
PM cycle.
Since we brought up the subject, just a word on loading...
A load representing the normal operating
load, or loading capacity needs to be
used if one is spending all this labor to expose
the switchgear (as well as time in
front of an arc flash potential) to make the
testing meaningful.
But commonly, some available noncritical
small load is used. The real load,
the critical load, has been switched over
to the back up switchgear. Which we trust
is in fine shape, since it’s last PM cycle.
With on-line, constant thermal monitoring,
one would know.
Due to the basic relationship of I2 x R
= W, it is critical that the proper load is
applied to the switchgear being tested that is the same
level as your load, or tests the capabilities
of your switchgear.
Notice, it’s not I x R , (which will solve
for Voltage), and it’s not a direct linear relationship.
The relationship for calculating
power in the connection includes I2,
(Current Squared) or 100Amps2 ;
For this example, lets use 1 milliOhm
(0.01 Ohm).
Sounds incident enough of a resistance
value?
(100Amps x 100Amps) = 10,000 x the
Resistance of the connection = Wattage
10,000 x 1milliOhm (.01 Ohm) =
100 Watts
“Wattage” = the energy/heat in the
connection, which you’re hoping is in
fine condition and checking based on
temperature.
But at 500Amps
(500Amps x 500Amps) = 250,000 x
the Resistance = Wattage
250,000 x 1milliOhm (.01 Ohm) =
2,500 Watts
Now at 2,000 Amps
(2,000Amps x 2,000Amps) =
4,000,000 x the Resistance = Wattage
4,000,000 x 1milliOhm (.01 Ohm) =
40,000 Watts!
So one can see the important role the
load current plays in actually finding, detecting
a bad joint.
Resistance of the connection, which
one may think is even subtler, plays a surprising
role in the heat within the connection.
If you would like more information
on the role relatively “small” resistant
numbers play in failures, please contact
us for “The Mighty Milliwatt” white paper;
bkern@psc-exertherm.com .
Back to the Hazard… I mean the “subjects” at hand and a
solution.
1) Labor intensive, mechanical intrusion
that can be the catalyst for an arc flash
event.
2) Having the proper loads for testing the
switchgear.
These two basic issues share a simple
common solution…
Monitor the health of the switchgear
while it’s closed and under normal operation
with the real load!
It’s that simple.
Being able to monitor the switchgear
while it’s closed eliminates the mechanical
intrusion that can cause arc flash events.
Keeping the switchgear cabinets assembled
and closed does not expose the electrician
to the possibility of an arc flash hazard.
To achieve system level loading, some
facilities rent temporary AC load banks.
As discussed above, this is much more accurate
than using a small token load. To
use these loads banks, proper installation
is important, as well as being to accommodate
and cool these large load banks.
Improper installation and connections
have resulted in outages and damaged
switchgear. So using the real load, under
normal every day operation, under normal
conditions is just not an intrusive act and
is a natural solution that will mitigate
many risks as well as arc flash.
IR is an accepted means of detecting the
heat energy from losses that emanated
from the resistance of a connection. Simply
install IR sensors within the switchgear
to monitor the connections 24/7.
No needed for an IR sensor at every
junction or bolted connection. The bus
bars within the switchgear conduct heat
very well.
The heat generated by the resistance of
the contacts within a breaker will conduct
out onto the bus bar very well. So even the
condition of a breaker’s contacts can be
evaluated before “opening” it. Again, as
with the bus bar connections, this constant
thermal monitoring while the switchgear
is closed gives a solid indication of the
health or potential hazard the breaker
poses before a worker interacts with it.
Such on-line constant thermal monitoring
(24, 7, 365) not only provides real
time data, and alarming, but also records
monitored temperatures. So now we can
evaluate the condition of the breaker, bus
bars, and any critical current carrying
components while under normal or heavy
loadings times.
If evaluation of the data, from either
monthly reviews, or from an alarm, indicate
maintenance is needed, the switchgear
can be de-energized, repairs performed, reassembled,
closed up and re-energized. So
as long as proper procedure is followed,
the personnel working on the switchgear
are never put in harms way of an arc flash
event during the maintenance. The only
time the switchgear is re-energized is after
it’s fully assembled and buttoned up as it
should be.
With on-line constant thermal monitoring,
the engineer can immediately, safely
check the condition of the repair while in
front of a PC monitor, not while standing
in front of a potential arc flash hazard.
Will future upgrades be detrimental to
aging equipment?
The health of the electrical infrastructure
can be evaluated after increases in the
load have occurred, such as the addition
of new servers. Simply compare the
recorded data temperature data from the
days before and after the upgrades.
With on-line constant thermal monitoring
we now can sharpen the image in our
crystal ball of the health and life of the
switchgear by providing true PdM while
mitigating risks of arc flash.
About the Author:
Bob Kern is the ExerTherm Product
Manager, with Power Service Concepts.
Power Service Concepts is the
authorized U.S. distributor for
ExerTherm.




















