When it comes to power system
design and operation,
there should be no greater
concern than safety. Not
only must electrical system designers implement
safeguards to protect equipment
and processes, they must also evaluate the
hazards associated with arc faults.
For example, in many electrical facilities,
it’s a common practice to set protective
device settings to high-interrupting
fault currents to avoid nuisance trips,
which result in undesired interruption and
costly shutdowns and re-starts. However,
protective device settings may perform
poorly when it comes to protecting the
people working on energized equipment
in the event of a low-voltage arc fault.
Protective device trip settings for many
electrical facilities have been set solely
based on bolted three-phase short-circuit
criteria. However, low-voltage arc faults
(< 1.0 kV) may produce a current magnitude
much smaller than the circuit’s maximum
available 3-phase bolted shortcircuit
current. Of course, the incident energy
expected to be released should be
smaller at lower current magnitudes; however,
in some situations it may turn out
that overcurrent devices take much longer
to trip, and thus the release of incident energy
could last for seconds or minutes.
Exponentially longer arc fault clearing
times encountered at steep portions of the
time current characteristic curves (TCCs)
translate into much higher amounts of incident
energy release (see Figure 1).
This article discusses methods available
for calculating the incident energy
released by an arc fault in low-voltage
equipment. It also presents considerations
which should be made to determine the
worst-possible hazard associated with energized
work at different locations of the
equipment. In addition, it will cover
methods to reduce the hazard level like
maintenance mode settings and arc flash
sensor relays.
Two Calculation Methods
The majority of the arc flash analyses
are performed using the IEEE 1584 and
NFPA 70E methods. Both methods consider
the low-current magnitude phenomenon,
but have different ways of
accounting for its effect in the calculation
of the incident energy.
The NFPA 70E 2004 method recommends
that the incident energy for equipment
600 Volts and below be determined
from the “maximum” and “minimum”
short-circuit currents. In fact, in this model
a 62% reduction of the maximum available
short-circuit current is recommended
to determine situations at which the upstream
overcurrent device could take seconds
or minutes to operate (NFPA 70E
2004 Annex D.6). This reduction percent
corresponds to the industry accepted minimum
current level for self sustaining arc
faults. Equation [D.6.2 (a)] can then be
used to calculate the incident energy.
The IEEE 1584TM-2002 and 2004a “IEEE Guide for Performing Arc-Flash
Hazard Calculations” (sections 5.1 to 5.5)
provides a second method to calculate the
incident energy for low-voltage equipment.
The IEEE 1584 empirically-derived
equations can predict very low arc fault
current values. IEEE 1584 2002 equation 1 can be used to determine
the magnitude of the actual arc
fault current (instead of the available
short-circuit current as used by the NFPA
70E method).
In fact, for the simple electrical system
described in this article, the calculated
arcing current magnitude can be as low
as 45% of the maximum available bolted
3-phase short-circuit current. The 45%
value already accounts for the additional
15% reduction recommended by IEEE
1584 for systems with nominal voltages
less than 1000 Volts (section 5.2 of IEEE
1584a 2004).
The lower magnitude of low-voltage
arc faults raises arc flash analysis problems.
The results can be very different depending
on which method is used to
determine the incident energy results, but
no matter what analysis method is used to
perform arc flash analysis, it may be necessary
to run several variations in the arc
fault current magnitude to attain with certainty
the absolute highest incident energy
value which can be released.
Identifying Low-Voltage Arc
Hazards
To properly identify the hazards of low voltage
arcs, it is necessary to consider all
the possible arc locations and the protective
devices involved for protecting the
circuit. Furthermore, it may be necessary
to run two sets of calculations (i.e., one
for maximum and a second for the minimum
currents).
To illustrate how to determine the hazards
of low-voltage arcs, we can perform
arc flash analysis at two locations for the
system shown in Figure 2. This system has a typical arrangement for
overcurrent and short-circuit
protection. The 1.5 MVA transformer
is fed from a 177
MVAsc utility connection, and
it is protected for short-circuit
with a 100-Amp, 15.5 kV standard
speed fuse located on the
13.8 kV primary voltage side.
The transformer feeds a 480-
Volt switchgear with a main
2400-Amp power circuit
breaker with a solid state trip
device.
Using power system
analysis software,
we can simulate an arc fault on
the
switchgear bus bars at the “SWGR B” location. Figure 2
shows the computer program results
for a fault at this bus using
the IEEE 1584 2004a method.
The NFPA 70E method is also
used to evaluate the arc fault at
the same location for both maximum
and minimum expected
short-circuit currents. The protective
device expected to trip the
arc fault is the main breaker CB5.
The results of the four different
arc fault analysis are listed in Table 1.
If you use the maximum short-circuit
current to determine the incident energy,
the results reveal that because of the fast
action of the instantaneous part of the
solid state trip device in CB5, the incident
energy released at the bus is 2.69 cal/cm?
with a hazard category of 1, based on
NFPA 70E-2004, Table 130.7(C)(11).
However, if you use the minimum
short-circuit current, the resulting incident
energy can reach as high as 25 cal/cm?
(category 4). This is caused by the much
longer clearing time of CB5.
The IEEE 1584 method predicts hazard
category 3 results (12.5 to 14.51 cal/cm?)
as the worst-case scenarios. The IEEE
1584 method provides the more accurate results in this case since it is using the actual
arcing current (Ia) to determine the
time it takes the CB5 breaker to operate.
The previous simulation may not be
sufficient to establish the worst-case incident
energy for this low-voltage equipment.
If you simulate an arc fault at the
main breaker compartment, as shown in
the Figure 3, the incident energy released
at this location can be much larger since
the primary protective device would be
Fuse2 with a longer clearing time.
The results shown in Table 2 indicate
that the incident energy released for a fault
located at the line (incoming) side of the
circuit breaker CB5 can be far more dangerous
because of the longer operating
time of the fuse. Figure 1 shows the Time
Current Characteristic (TCC) of Fuse2
along with the expected fault clearing
times for the minimum, maximum and
arcing fault values.
Note that a small reduction in the fault
current leads to a much longer total
clearing time. There have been several
documented arc flash incidents in low voltage
equipment which have lasted for
several seconds or even minutes because
of the slow response of upstream protective
devices.
Note 1: Ibf or Ia denotes whether the
bolted 3-phase short-circuit (Ibf) or the
arcing current (Ia) were used to determine
the fault clearing time.
Note 2: The Fuse total clearing time
was determined from the current at the
13.8 kV base. (see Figure 1)
Reducing the Hazard Risk
One of the most effective ways to reduce
the hazard associated with low-current
magnitude arc faults in low-voltage
equipment is to modify the settings of the
protective devices to reduce the arc fault
clearing time. Typically main power circuit
breakers do not have their instantainstantaneous
response enabled because of coordination
with downstream devices. For
the case of the arc faults at the bus, temporarily
setting the instantaneous pickup
of the main power circuit breaker to the
left of the lowest expected arc fault current
value should significantly reduce the
fault clearing time.
There are devices available in the market which have “Maintenance” modes
which automatically override the normal
protective device coordination settings
and introduce an instantaneous pickup setting,
which is low enough to pickup the
arc fault current magnitude. When the energized
electrical work or maintenance is
complete, the main protective device can
be set back to normal operation settings. Figure 4 illustrates
the maintenance mode settings and
the fault arrow marked as “Minimum Arcing
Current” shows the absolute lowest
arcing current magnitude.
The addition and reduction of instantaneous
pickup settings is just one way
to reduce the hazard associated with
low-voltage arcs. Light detecting relays
or “Arc Flash Sensors” are devices
which detect the light emitted by the arc
fault. In the event of an arc, the light
sensors send a trip signal to relay which
in turn can trip the breaker in less than 2
cycles.
Arc sensors are also used in combination
with overcurrent relays. The arc sensor
relay would only send the tripping
signal if both overcurrent and light sensors
indicate the presence of an arc fault.
This more advanced setup helps to prevent
nuisance trips caused by non arc
flash related light sources.
The bottom line is that no matter what
analysis method is chosen for the analysis
(IEEE 1584 or NFPA 70E or a combination),
it is important to consider the
extremely low magnitudes of the arc
faults in low-voltage equipment. Both
the maximum and minimum arc fault current levels need to be analyzed to
properly evaluate the hazard of energized
electrical work.
Serious consideration should be given
to not performing energized work in high
risk locations which depend on upstream
overcurrent protective devices to trip the
fault, unless some method is used to minimize
the hazard. These strategies for reducing the incident energy are just some
of several available to reduce or liminate
the risk of potentially fatal arc flash
incidents.
Albert Marroquin is a senior electrical
engineer and testing manager for Irvine,
Calif.-based Operation Technology, Inc.
Evaluating the Hazards
of Low-Voltage Arcs




















