Electrical testing is essential to the
evaluation and maintenance of
motor
performance and life.
There are a variety of properties
that can be tested, with a broad range from
the simple and general tests, like voltage
measurement, to the highly complex and
specific, like surge testing. (This latter is a
technique that pinpoints turn-to-turn
shorts.) They are too diverse to all be covered
comprehensively as a single topic,
but a general method that is universal and
indispensable is that of insulation testing.
In its basic terms, an insulation tester
applies a high dc voltage across an insulation
barrier, measures the amount of current
(commonly called “leakage”) that
flows through the insulation, and applies
Ohm’s Law to calculate the resistance of
the insulation. The basic theory is quite
simple, but the testers themselves are
complex, primarily because they must generate a high voltage and be able to accurately
measure a miniscule current.
There is no perfect insulator. Apply
enough voltage and any material can
break down (think of a lightning strike!).
But by applying the test voltage across the
insulation, the tester is establishing a
highly atypical “circuit” in which an insulating
material is being forced to act as a “conductor.” Obviously, it is not going to
conduct very much, so the tester must be
able to sense currents on the nano-amp
level and below. These are the principle
characteristics of an insulation tester. Because
resistance is high, measurements are
made in units of meg-(millions of)ohms.
A caution about voltage supply is in order.
Many “economy-level” testers provide
only nominal test voltage selection.
That is to say, a given voltage selection
may only provide that voltage over a limited
portion of the resistance range. To
avoid this problem, the tester should be
provided with a load curve of output voltage
versus load resistance. This curve
should indicate a fast rise up to full selected
voltage at a level of 1 to 5
megohms, then maintain that voltage
throughout the remaining range. While dc
insulation testing is non-destructive (as
opposed to “high-pot” testing), there are
limits where severely deteriorated insulation
is concerned. To avoid any further
damage to insulation that is already near
breakdown, test current is limited. Since
IEEE Standard 43 recommends never less
than two megohms for rotating machinery,
a simple application of Ohm’s Law
indicates that at a typical 1000 volt test,
this represents no more than half a milliamp!
Consequently, testers need output
no more than a few milliamps to be able
to cover the full range of anything fit to
be considered as insulation. Once this
limit is reached, there is nothing but for
the voltage to drop, further protecting a
test item that is on the unacceptable end
of the scale. The voltage should rise
sharply through the low end of the range,
then maintain full selected voltage
through “good” values. A poorly designed
tester will exhibit a slow rise, not achieving
full voltage until well up into the
range. The critical range of values, where
the motor is still operating but is approaching
a need for maintenance, will be
getting tested at deceptively low voltages
and yielding potentially misleading results.
The benefit of this testing is that the
readings can be used like the odometer on
a car, to give an idea of the working age
of the motor, how much can be reasonably
expected of its performance, and
where it is on its life cycle. From the time
a motor is put into service, insulation
picks up moisture, dirt, and other contaminants,
suffers wear and tear, is carbonized
from voids and other
imperfections, or may be damaged by line
disturbances. From initially high values
(possibly tera-ohms), these factors will
cause insulation resistance to decline, often
at a fairly steady and predictable rate.
An insulation test is a quick and simple
maintenance check that captures the information
available from the aging
process, and by inference, reflects the
overall condition of the motor itself. Of
course, catastrophic failure can also occur,
as in flooding, fire or lightning strike.
An insulation test is typically performed
here also, but such events exemplify the
separation between the two broad areas of
testing: pass/fail and preventive maintenance.
Pass/fail testing is the more commonly
employed. A motor has failed, is performing
erratically, or tripping breakers.
An insulation test is performed to look for
breakdown. It may appear as a dead short
or unacceptably low reading (typically,
less than 2 megohms). In such applications,
a sophisticated tester is not required,
and the operator may not be concerned
about the actual readings. Experienced
personnel may look for direction of
pointer travel only, toward the low or high
end of the scale. If low, an electrical problem
exists, and more specific troubleshooting
can commence. If high, time
might be better spent looking for a mechanical
problem such as bearing wear.
Pointer travel is significant in insulation
testing as with no other type of test. It is
also frequently confusing and frustrating
to the uninitiated. Motor windings, by
their structure, possess a good deal of capacitance.
Each turn represents two conductors
separated by insulation: a tiny capacitor.
The larger the winding, the
greater the capacitance. Secondly, insulating
material itself will realign molecularly
under the influence of an applied
voltage field. This too represents a flow
of charging current called absorption. Because
of these charging effects, readings
start low and gradually rise as charging
goes to completion. What remains after
full charge is the current that flows as a
product of the level of imperfection of the
material called “leakage”. With the largest
windings this can take hours, an impractically
long test time. Therefore, special
procedures called test methods have been
worked out to bring the testing into workable
time frames and act as an aid in interpreting
results.
The second broad area of testing, preventive
maintenance, is more sophisticated.
High quality testers are advised
because these will have the range necessary
to measure equipment that is in the earliest stages of
its life cycle, preferably beginning with
an installation test. In such applications,
a simple pass/fail tester with limited range
will yield only an over range test, typically
called “infinity”. This is not a true
measurement, but merely an indication
that the motor has a resistance greater than
the sensitivity of the tester. Such an assurance
is satisfactory for pass/fail applications,
but does nothing to establish a
time line for life expectancy. It may be
years before resistance drifts down to
where it can be measured, with considerable
loss in flextime for scheduling routine
maintenance. There is no better way
to evaluate test results than comparison to
a previous test. Readings may be quite
high, and if evaluated singly, appear “good”. But if the motor is operating in a
hostile environment, possibly exposed to
corrosive fumes or high moisture, readings
may be dropping rapidly. Early detection
would allow time for corrective
action before significant damage could occur.
Conversely, comparatively “low”
readings holding steady probably indicate
a widely dispersed low level of harmless
leakage, so that critical maintenance time
can be spent on more pressing problems.
Standardized test methods can be judiciously
employed to help with test time
and interpretation. A number of methods
have been devised, and each “looks at”
the insulation in a different way. Except
for the most critical and high-capital
equipment, it is not practical to perform a
full regime of test methods. Rather, judicious
selection of the most appropriate to
a given set of circumstances can maximize
results while conserving test time.
Two broad categories of insulation failure
are pervasive contamination and localized
damage. Two of the most popular methods
are Polarization Index and Step Voltage.
Polarization Index, more popularly
known as “PI,”, takes advantage of the
differential beteen “harmless” charging
currents and damaging leakage. In healthy
equipment, leakage is small by comparison,
so the charging currents dominate
pointer travel. There will be a fairly large
difference between a reading at 1 minute
and at 10. When converted to a ratio,
numbers typically in the range of 2 to 4
are seen. But deteriorated insulation will
be dominated by leakage, which is constant for a given test voltage and will
mask the effects of charging. The 10-
minute reading will be similar to the 1-
minute, and a poor PI of less than 2 is the
result. The PI is good for detecting pervasive
contamination because the effect on
leakage versus charging current will be
readily apparent. It also solves a number
of practical problems. Dependence on a
knowledge of resistance values is eliminated
because whether they are in the tens,
hundreds or thousands of megohms, the
result will be the same. Therefore, the PI
is a good test where no prior records are
available.
PI is also useful on very large motors
for two reasons: time and voltage. Large
windings can take a prohibitively long
time to reach a stable reading, but that is
not necessary with PI. The 1- and 10-minute readings can be
relatively low on the time-resistance
curve; the result is still valid. Caution
must be taken with smaller windings,
however, as they may reach full charge
quickly and yield a low PI even though
perfectly “good.” Similarly, the tester
must have a good range so that it will not
over range before 10 minutes. “Infinity”
is not a number and cannot be used to calculate
a PI. The second advantage with
large motors is that they may have high
operating voltages that put “as rated” tests
beyond the test voltages of all but large,
expensive testers. PI can be performed
successfully at values below rated.
A Step Voltage Test is performed by
increasing the test voltage in steady increments
and observing the response of the
insulation readings. Voltages and time intervals
can be defined by the operator to
meet the demands of test equipment and
work schedule, but industry standard is
five voltages (such as 1, 2, 3, 4 and 5 kV)
in 1-minute intervals. Good insulation will
stand up to this treatment, but deteriorated
insulation will open more leakage paths
with each increase, and readings will
steadily drop. These two tests, and most other standard methods, are not mutually
exclusive, but complementary. Each will
reveal a variety of problems, but each has
individual strengths. Step Voltage is a
good test for recognizing elusive intermittent
failures that can arise from localized
damage in otherwise "good”
insulation. A carbon track that has burned
through or a pinhole caused by a voltage
spike may be lying against an air gap instead
of direct contact to ground. An insulation
resistance test may still yield a
high reading and overlook the critical
flaw. But Step Voltage can arc the gap and
expose the problem. Another specialized
problem is dry and brittle insulation on
old motors. Failure is imminent, but this
type of insulation will often yield deceptively
high readings. An unnaturally high
PI will reveal the condition, but can be
mistaken for a “good” reading by those
not familiar with past history. A Step
Voltage can be expected to draw increasing
amounts of leakage through cracks in
the dried insulation with each voltage increment
and readily reveal the condition.
The accepted standard for electric motor
testing is IEEE Std 43-2000: Recommended
Practice for Testing Insulation
Resistance of Rotating Machinery, published
by The Institute of Electrical and
Electronics Engineers. This standard was revised in
2000 in order to take into account the effects
that newer types of insulation have
on standard testing procedures and interpretation
of results. Industry practices, in
the interest of time, may gang all windings
and test simultaneously to ground or
case. But IEEE recommends phases be
tested individually, with remaining phases
and stator core or rotor body connected to
a common ground. This will reveal leakage
between phases, as well as phase-to-ground.
Similarly, testing can be done
through external equipment like motor
controls, but it must be understood that
these will be included in the measurement,
and bring it down. IEEE prefers that external
equipment be disconnected. Testers
may also have guard terminals, which act
as shunts for one or more parallel leakage
paths. In a complex piece of equipment
like a motor, there may be several leakage
paths. These can be examined more
specifically by elimination of one of more
through guard connection. For instance,
stator to rotor leakage can be measured
with ground leakage guarded.
The revision includes a table of recommended
test voltages based on equipment
rating. In response to newer insulation
types, the recommended test voltages
have been increased up to 10 kV for motors
rated at 12 kV and above. Both basic
insulation resistance and polarization index
tests are recommended, with one or
the other performed on equipment rated
less than 10,000 kVA, and both tests suggested
for equipment rated higher. There
are also some interesting observations for
atypical windings. Large turbine generators
may have unencapsulated field windings
where little absorption can take place,
so that a PI is not a recommended test. It
is also advisable for the operator to have
knowledge of the basic schematic in order
to avoid testing errors. For instance,
windings of some induction motors may
not be insulated from the rotor body, so
that a PI is not possible.
Traditional notions about PI testing are
also undergoing an upgrade as the result
of new insulation types. Absorption currents
may decay to near zero in much
shorter time frames, making the traditional
1 to 10 ratio dubious. Accordingly, newer
definitions have incorporated 1-minute to
5-minute and 30-second to 1-minute ratios.
An alternative suggestion is to record
the reading every minute until three consecutive
intervals yield the same result.
The caveat for all of these newer methods
is that they are not standardized, and there
hasn’t been enough data collected to set
new pass/fail values. IEEE requests such
information be forwarded by field sources.
In summary, insulation testing offers a
quick and convenient window into the
electrical condition of a motor, and provides
a reliable basis upon which further
maintenance and troubleshooting decisions
can be made.























